When button testing units in sequence it is important to wait 15 seconds plus a further 6 seconds per
repeater between button tests (e.g. for a system with 10 repeaters, time to wait: 15 seconds + 10 x 6
seconds = 75 seconds between button tests).
Finally attach the label provided to the distribution board to identify the alarm circuits.
(Note: If it is necessary to clear House Codes see section 12, page 32 - Technical Specification).
The “Repeater” Function
All Ei262 CO Alarms are set as “Repeater” units as supplied. The function of a Repeater unit is to receive
and then re-transmit the RF signals. This provides multiple signal paths throughout the installation to give
improved RF signal reliability (with 3 or more RadioLINK units).
Note the “Repeater” function is not operational until all the units are put in to House Code mode.
The operation of the “Repeaters” can be observed as each unit turns on its RadioLINK Indicator light as a
RadioLINK message is being repeated.
(Note: If it is necessary to disable the Repeater function see section 12, page 34 - Technical Specification).
4.2.2 RadioLINK Accessories
When using RadioLINK accessories simply install all the devices as per their instructions first. Then
follow the house coding and checking procedure described in 4.2.1 above.
4.3 Hardwired Interconnect - The Ei262 also provides a facility for hardwired interconnection:
With interconnected alarms, when one unit detects CO all units alarm. All horns will sound but only units
detecting CO will flash their alarm red lights.
A combined maximum of twelve Ei262 CO Alarms may be interconnected along with an Ei128RBU &
Ei128COV relay module (see “ACCESSORIES” section).
Alternatively, up to twelve Ei262 CO Alarms and Ei161RC/Ei164RC/Ei166RC/Ei2110 Smoke/Heat/Fire
Alarms in total, may be interconnected provided an Ei1529RC Remote Control is used in the system
(see “ACCESSORIES” section).
20